Fiber optic loss budget calculator

Add up the loss on a fiber span (cable, connectors and splices) and check it against your power budget before you light it. Single-mode and multimode, with the published attenuation built in.

The span
Result
Link closes with margin
2.13 dB
total link loss
9.87 dB
margin left
69,366 ft
max reach at this margin
Breakdown: 0.53 dB cable + 1 dB connectors + 0.6 dB splices = 2.13 dB against a 12 dB budget. Keeping about 3 dB in reserve covers aging, a dirty connector, and a future repair splice.

What is a fiber optic loss budget? It is the accounting of how much optical power a link loses end to end, compared to how much the equipment can afford to lose. You add up the loss from the cable itself, every connector, and every splice, then compare that total to the power budget of the transceivers. If the loss is less than the budget, the link works; the difference is your margin.

Common questions

What is a fiber optic loss budget?

It is the accounting of how much optical power a link loses end to end, compared to how much the equipment can afford to lose. You add up the loss from the cable itself, every connector, and every splice, then compare that total to the power budget of the transceivers. If the loss is less than the budget, the link works; the difference is your margin.

How do I calculate fiber link loss?

Multiply the length in kilometers by the fiber's attenuation in dB per km, add the number of connectors times the per-connector loss, and add the number of splices times the per-splice loss. Total loss equals cable plus connectors plus splices. The calculator above does this and checks it against your budget.

How much loss does a connector or splice add?

TIA-568 allows up to 0.75 dB per mated connector pair, though clean, well-seated connectors are often nearer 0.3 dB. A fusion splice is typically about 0.1 dB and is allowed up to 0.3; a mechanical splice runs closer to 0.3. The calculator defaults to 0.5 dB per connector and 0.1 dB per fusion splice, both editable.

What is the attenuation of single-mode vs multimode fiber?

Single-mode OS2 loses roughly 0.35 dB per km at 1310 nm and about 0.22 dB per km at 1550 nm, which is why long outside-plant runs use it. Multimode OM3/OM4 loses about 3.0 dB per km at 850 nm and around 1.5 dB per km at 1300 nm, fine for short in-building runs but far lossier over distance.

How much margin should a fiber link have?

Keep some headroom rather than running to zero. A common target is about 3 dB of margin above the calculated loss to cover fiber aging, a connector that gets dirty, and the occasional repair splice added later. A link that only just closes today can drift out of budget over its life.

What is the power budget of the transceivers?

The power budget is the transmit power minus the receiver sensitivity, both read off the optics datasheet in dBm. For example a transmitter at -3 dBm into a receiver good to -20 dBm gives a 17 dB budget. Enter it directly, or use the Tx and Rx fields in the calculator to work it out.